Your Cart

UPS Hyundai 3 Phases Transformer Base HD-10K3~HD-60K3

UPS Hyundai 3 Phases Transformer Base HD-10K3~HD-60K3
Giá: Liên Hệ
Giá Kèm Thuế: Liên Hệ
INPUT
Voltage range+/-25%
Frequency range50/60Hz ± 5Hz
Power factor>0.95 (with filter)
Bypass voltage range20% (settable)
Delayed start of rectifier1~ 300s (settable via dispaly panel)
ECO voltage range10% (settable)
OUTPUT
Voltage range380V/400V/415Vac
Voltage regulation1%
Frequency rangeSynchronized with utility in mains mode; 50/60Hz 0.1% in battery mode
Crest ratio3:1
Power factor>- 0.95 (with filter)
Harmonic distortion<= 2% (linear load); <= 5% (non-linear load)
Transfer timeAC mode to battery mode: 0s Inverter mode to bypass mode: 0 ms Inverter mode to ECO mode: 5 ~ 10s
Overload capability105% long time runnning, 105% ~ 110% for 1 h; 110% ~ 125% for 10 min, 125% ~ 150% for 1 min, 150% ~ 200% for 200ms, > 200% for 100ms
BATTERIES
DC voltage12V x configured battery number (settable via display panel)
Number of battery28 ~ 32 pcs (settable)
Charging curent(max)10A /settable
OTHERS
Noise level55dB, 60dB, 65dB
ProtectionShort - circuit - overload - overvoltae - undervoltage - low battery - overtemperature - fan fault